Eclipse
Model 706
®
F
fieldbus
™
OUndatIOn
Operating Manual
Software Version 1.x
High Performance, 4th Generation
Guided Wave Radar
Level Transmitter
Use in conjunction with
I&O manual BE 57-606
Related Manuals for Magnetrol Eclipse 706
Summary of Contents for Magnetrol Eclipse 706
-
Page 1
Eclipse Model 706 ® fieldbus ™ OUndatIOn Operating Manual Software Version 1.x High Performance, 4th Generation Guided Wave Radar Level Transmitter Use in conjunction with I&O manual BE 57-606… -
Page 3: Table Of Contents
® Eclipse Model 706 GWR transmitter with F Fieldbus Output ™ OUNDATION Table of Contents 1.0 F fieldbus ……….4 4.0 Model 706 Transmitter Configuration ……32 ™ OUNDATION 1.1 Overview…………..4 4.1 Configuration Information ……..32 1.2 Device Description (DD)……….5 4.2 Menu Transversal and Data Entry ……33 1.2.1 F fieldbus ™…
-
Page 4: Foundation Fieldbus
Fieldbus ™ OUNDATION Overview fieldbus is a digital communications system ™ OUNDATION that serially interconnects devices in the field. A Fieldbus system is similar to a Distributed Control System (DCS) with two exceptions: • Although a Foundation fieldbus system can use the same ™…
-
Page 5: Device Description (Dd)
Device Description (DD) An important requirement of Fieldbus devices is the concept of interoperability, defined as “the ability to operate multiple devices in the same system, regardless of manufac- turer, without loss of functionality.” Device Description (DD) technology is used to achieve this interoperability.
-
Page 6: Intrinsic Safety
Intrinsic Safety The H1 physical layer supports Intrinsic Safety (IS) applica- tions with bus-powered devices. To accomplish this, an Intrinsically Safe barrier or galvanic isolator is placed between the power supply in the safe area and the device in the hazardous area. H1 also supports the Fieldbus Intrinsically Safe Concept (FISCO) model which allows more field devices in a net- work.
-
Page 7: Standard Function Blocks
Standard Function Blocks Overview The function of a F fieldbus device is deter- ™ OUNDATION mined by the arrangement of a system of blocks defined by the Fieldbus foundation. The types of blocks used in a typi- cal User Application are described as either Standard or Advanced.
-
Page 8: Universal Fieldbus Block Parameters
2.1.1 Universal fieldbus Block Parameters The following are general descriptions of the parameters common to all function blocks. Additional information for a given parameter may be described later in a section that describes the specific block. ST_REV: a read only parameter that gives the revision level of the static data associated with the block.
-
Page 9: Resource Block (Rb)
Under normal operating conditions, it should be “On-Line.” DD_RESOURCE: A string identifying the tag of the resource that contains the Device Description for this device. MANUFAC_ID: Contains Magnetrol International’s fieldbus ™ manufacturer’s ID number, which is OUNDATION 0x000156.
-
Page 10
CYCLE_TYPE: Identifies the block execution methods that are available. CYCLE_SEL: Allows the user to select the block execution method. MIN_CYCLE_T: The time duration of the shortest cycle interval. It puts a lower limit on the scheduling of the resource. NV_CYCLE_T: The minimum time interval between copies of non-volatile (NV) parameters to NV memory. -
Page 11: Additional Resource Block Parameters
BLOCK_ALM (Block Alarm): Is used for configuration, hardware, connection, or system problems in the block. The cause of any specific alert is entered in the subcode field. ALARM_SUM (Alarm Summary): Contains the current alert status, the unacknowledged states, the unreported states, and the disabled states of the alarms associated with the block.
-
Page 12
FD_OFFSPEC_MAP: Maps conditions to be detected as active for the OFFSPEC alarm category. FD_MAINT_MAP: Maps conditions to be detected as active for the MAINT alarm category. FD_CHECK_MAP: Maps conditions to be detected as active for the CHECK alarm category. FD_FAIL_MASK: Used to suppress an alarm from being broadcast for single or multiple conditions that are active in the FAIL alarm category. -
Page 13: Transducer (Tb)
“simulation” indicator in the Block Error parameter. SERIAL_NUMBER: Read-only parameter that corresponds to “Magnetrol Serial Number” in the Transducer Block. FIRMWARE_VERSION: Read-only parameter that corre- sponds to “Firmware Version” in the Transducer Block. HARDWARE_VERSION: Read-only parameter that corre- sponds to “Hardware Version”…
-
Page 14: Tb Parameters
2.3.1 transducer Block Parameters The first six parameters in the TRANSDUCER Block are the universal parameters discussed in section 2.1.1. After the universal parameters, six additional parameters are required for Transducer Blocks. The most notable of these parame- ters are UPDATE_EVT and BLOCK_ALM. It should be noted that these six additional parameters must exist but do not have to be implemented.
-
Page 15: Configuration Parameters
On the other hand, part of the advantage of F OUNDATION fieldbus™ is to provide the ability to monitor changes and make adjustments to a transmitter. The Fieldbus™ concept allows a user to make adjustments if deemed necessary. 2.3.4 Eclipse Model 706 FF device-Specific Configuration Parameters Please refer to ECLIPSE Model 706 I/O Manual BE 57-606 for detailed information on the Model 706 device-specific…
-
Page 16
ST_REV: a read only parameter that gives the revision level of the static data associated with the block. This parameter will be incremented each time a static parameter attribute value is written and is a vehicle for tracking changes in static parameter attributes. -
Page 17
CHANNEL: The number of the logical hardware channel that is connected to this I/O block. (This information defines the transducer to be used going to or from the phys- ical world). L_TYPE: Determines if the values passed by the transducer block to the AI block may be used directly (Direct), or if the value is in different units and must be converted linearly (Indirect), using the input range defined for the transducer… -
Page 18: Ai Block Diagnostics
LO_LO_ALM: The status for low-low alarm and its associ- ated time stamp. BLOCK_ERR_DESC: Reports more specific details regard- ing some errors reported through BLOCK_ERR. The MODE_BLK parameter (within both the TB and AI Blocks) must be set to AUTO to pass the PV Value through the AI to the network.
-
Page 19: Ai Out Display Screens
NOTE: There are many reasons that AI block Out values can deviate from the measurement value originating in the Transducer block, and because the keypad and local display will only pro- vide access to Transducer block parameters, there is no way to change (or view) the other fieldbus configuration items affecting the AI block output using the keypad and LCD.
-
Page 20: Ai Block Configuration
2.4.4 aI Block Configuration Below are shown some examples of various typical AI Block configurations. Example 1: standard Configuration configuration for trans- mitter with probe of Probe Length length PL inches or cm. Transducer Level Offset AI Block Output Block + [setup by factory as [To FF segment] XD Scale EU at 0%…
-
Page 21: Simulation Feature
2.4.5 Simulation Feature The ECLIPSE Model 706 with F fieldbus ™ OUNDATION supports the Simulate feature in the Analog Input block. The Simulate feature is typically used to exercise the opera- tion of an AI block by simulating a TRANSDUCER block input.
-
Page 22
BKCAL_IN: The analog input value and status for another blocks BKCAL_OUT output. BKCAL_HYS: The amount the output must change away from its output limit before the limit status is turned off, expressed as a percent of the span of the output. BKCAL_OUT: The value and status required by the BKCAL_IN input for another block. -
Page 23
IN: The connection for the PV input from another block. LO_ALM: The LO alarm data. LO_LIM: The setting for the alarm limit used to detect the LO alarm condition. LO_LO_ALM: The LO _LO alarm data. LO_LO_LIM: The setting for the alarm limit used to detect the LO_LO alarm condition. -
Page 24: Advanced Function Blocks
STATUS_OPTS: Allows one to select options for status handling and processing. STRATEGY: Can be used to identify grouping of blocks. ST_REV: The revision level of the static data associated with the function block. TAG_DESC: The user description of the intended applica- tion of the block.
-
Page 25
TOTAL_SP: The set point for a batch totalization. OUT: The block output value and status. OUT_RANGE: The high and low scale values, engineering units code, and number of digits to the right of the decimal point associated with OUT. GRAND_DENY: Options for controlling access of host computers and local control panels to operating, tuning, and alarm parameters of the block (not used by the device). -
Page 26: Arithmetic Block (Ar)
INTEG_OPTIONS : A bit string to configure the type of input (rate or accumulative) used in each input, the flow direction to be considered in the totalization, the status to be considered in TOTAL and if the totalization residue should be used in the next batch (only when INTEG_TYPE=UP_AUTO or DN_AUTO).
-
Page 27
The nine arithmetic functions are: • Flow Compensation Linear • Flow Compensation Square Root • Flow Compensation Approximate • Btu Flow • Traditional Multiply and Divide • Average • Summer • Fourth Order Polynomial • Simple HTG Compensate Level ST_REV: The revision level of the static data associated with the function block. -
Page 28
GRANT_DENY: Options for controlling access of host computers and local control panels to operating, tuning, and alarm parameters of the block. INPUT_OPTIONS: Option bit string for handling the status of the auxiliary inputs. IN: The block input value and status. IN_LO: Input of the low range transmitter, in a range extension application. -
Page 29: Input Selector Block (Isel)
BLOCK_ERR_DESC: Reports more specific details regard- ing some errors reported through BLOCK_ERR. 3.3 Input Selector Block (IS) The Input Selector (IS) function block can be used to select the first good, maximum, minimum, or average of as many as four input values and place it at the output. The block supports signal status propagation.
-
Page 30: Signal Characterizer Block (Sc)
IN_2: The block input value and status. IN_3: The block input value and status. IN_4: The block input value and status. DISABLE_1: Parameter to switch off the input from being used 0- Use, 1 — Disable. DISABLE_2: Parameter to switch off the input from being used 0- Use, 1 — Disable.
-
Page 31
TAG_DESC: The user description of the intended applica- tion of the block. STRATEGY: The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block. ALERT_KEY: The identification number of the plant unit. -
Page 32: Model 706 Transmitter Configuration
4.0 Model 706 Transmitter Configuration Although the ECLIPSE Model 706 transmitter can be delivered pre-configured from the factory, it can also be eas- ily reconfigured in the shop or at the installation using the local LCD/Keypad. Bench configuration provides a conve- nient and efficient way to set up the transmitter before going to the tank site to complete the installation.
-
Page 33: Menu Transversal And Data Entry
4.2 Menu Traversal and Data Entry The four push buttons offer various forms of functionality for navigation and data entry. The Model 706 user interface is hierarchical in nature, best described as a tree structure. Each level in the tree contains one or more items.
-
Page 34: Entering Numeric Data Using Digit Entry
4.2.3 Entering Numeric Data Using Digit Entry This method is used to input numeric data, e.g., Probe Length or level offset. Push button Keystroke Action Moves up to the next highest digit (0,1,2,3,..,9 or decimal point). If held down the digits scroll until the push button is released.
-
Page 35: Enter Character Data
4.2.5 Entering Character Data This method is used for parameters requiring alphanumeric character entry, such as for entering tags, etc. General Menu Notes: Push button Keystroke Action Moves to the previous character (Z…Y…X…W). If held down, the characters scroll until the push button is released.
-
Page 36: Model 706 Menu: Step-By-Step Procedure
This password will be provided, when necessary, by Factory technical support. Factory Password Calibration-related and other factory settings are further protected by a Factory Password. 4.4 Model 706 Menu: Step-By-Step Procedure The following tables provide a complete explanation of the software menus displayed by the ECLIPSE transmitter.
-
Page 37
MAIN MENU Pressing any key on the Home Screen will present the Main Menu, consisting of three basic menu labels shown in all capital letters. DEVICE SETUP DIAGNOSTICS MEASURED VALUES As shown, the reverse video represents a cursor identifying the selected item, which will appear in reverse video on the LCD. -
Page 38: Model 706 Configuration Menu: Device Setup
Home Screen Probe Mount: Main Menu Flange Device Setup Quick Start NPT/Flushing Identity Product Name (read only) BSP/Flushing Magnetrol S/N (read only) Flange/Flushing Hardware Version (read only) Hygienic Firmware Version (read only) Physical Device Tag Device Address Level Units: Date Code…
-
Page 39
2.6.5 Model 706 Configuration Menu — device Setup Model 706 Configuration Menu — Device Setup Home Screen Level Units: Probe Model: Inches 7YD Coax HTHP Main Menu Feet 7YF Sngl Rod Tanks Millimeters 7YG Sngl Rod Cages Device Setup Quick Start Centimeters 7YJ Sngl Rod HTHP Cages Identity… -
Page 40
4.5 Model 706 Configuration Menu — Device Setup Home Screen Main Menu Device Setup Quick Start Identity Basic Config Measurement Type: I/O Config Level Only Display Config Interface and Level Advanced Config Volume and Level Factory Config Flow System Units Level Units: Probe Model: Flow Units:… -
Page 41
4.5 Model 706 Configuration Menu — Device Setup Home Screen Main Menu Device Setup Quick Start Identity Basic Config Display Config Language: Head: Probe Buildup: Advanced Config English (Flow mode only) (Buildup Detection = On) Factory Config French Hide Hide German View View… -
Page 42
4.5 Model 706 Configuration Menu — Device Setup Home Screen Main Menu Device Setup Quick Start Identity Basic Config Display Config Advanced Config Factory Config Sensitivity: Sloped End Dist: Reject Curve Mode: 0 to 100 echo strength units (used when Lvl Thresh Mode is Level Sloped) Distance… -
Page 43
4.5 Model 706 Configuration Menu — Device Setup Home Screen Main Menu Device Setup Quick Start Identity Basic Config Display Config Advanced Config Factory Config Fiducial Gain: 0 to 255 (read only) Fid Threshold Value SZ Hysteresis (Safe Zone Hysteresis): (not used when Safe Zone Alarm is None) 0 to 100 feet (0 to 30 m) -
Page 44: Troubleshooting And Diagnostics
5.0 Troubleshooting and Diagnostics The ECLIPSE Model 706 transmitter is designed and engi- neered for trouble-free operation over a wide range of oper- ating conditions. The transmitter continuously runs a series of internal self-tests and displays helpful messages on the large graphic liquid crystal display (LCD) when attention is required.
-
Page 45: Diagnostics (Namur Ne 107)
While changing any transmitter parameters using the local display or through a system configuration tool (with the MODE_BLK in OOS), the output might be inaccurate because of the changing parameters. When the device is set to OOS, the TRANSDUCER BLOCK will still output level but the QUALITY will be shown as “Bad”…
-
Page 46
In essence, this approach ensures that the right diagnostic information is available to the right person-at the right time. In addition, it allows diagnostics to be applied, as most appropriate, for a particular plant application (such as process control engineering or asset management mainte- nance). -
Page 47: Diagnostic Indication Simulation
No Probe Torque HF nut. Failure No Probe Connected. Clean gold pin on transmitter and socket on probe. Contact MAGNETROL Technical Support. Torque HF nut. Clean gold pin on transmitter and socket on probe. No Fiducial Check settings: Failure Reference signal too weak to detect.
-
Page 48
5.1.3 diagnostic Indicator table default Priority Indicator name Explanation Remedy Category Check settings: Dielectric Range No Echoes Sensitivity Failure No signal detected anywhere on probe. EoP Thresh Value Increase Sensitivity. Lower EoP Thresh. View Echo Curve. Check settings: Upper Dielectric, Echo Lost Blocking Distance, Signal from upper liquid too weak to… -
Page 49
Error Internal signal timing out of limits causing Out of Spec Replace transmitter electronics. inaccurate distance measurement. Contact MAGNETROL Technical Support. High Elec Temp Electronics too hot. May compromise Shield transmitter from heat source or Out of Spec level measurement or damage increase air circulation. -
Page 50: Diagnostic Help
ITEMS from the top level of the DIAGNOSTICS tree. When Present Status is highlighted, the highest MAGNETROL priority active diagnostic indicator (numer- ically lowest in Table 5.1.3) is displayed on the bottom LCD line as shown above. Pressing the ENTER key moves…
-
Page 51: Diagnostic Parameters
ECHO HISTORY SETUP – The Model 706 contains the unique and powerful feature that allows waveforms to be automatically captured based on Diagnostic Events, Time or both. This menu contains those parameters that configure that feature. Eleven (11) waveforms can be saved directly into the trans- mitter.
-
Page 52
diagnostic/Condition Process Variables Quality Sub-status Limit All PVs except No Echoes Sensor Failure Constant limited Elec Temperature All PVs except Lvl Below ProbeEnd Sensor Failure Constant limited Elec Temperature All PVs except EoP Below ProbeEnd Sensor Failure Constant limited Elec Temperature Software Error All PVs Device Failure… -
Page 53
diagnostic/Condition Process Variables Quality Sub-status Limit All PVs except Initializing Uncertain Initial Value Constant limited Elec Temperature Distance Good Non-Specific High limited Level Ifc Level Upper Thickness Good Non-Specific Low limited Volume Dry Probe Flow Head NR Totalizer Good Non-Specific Constant limited R Totalizer TB Config Changed… -
Page 54: Foundation
fieldbus ™ Segment Checklist 5.3 F OUNDATION There can be several reasons for a F fieldbus ™ OUNDATION installation to be in a faulty condition. In order to ensure that communication can be established, the following requirements must be met. •…
-
Page 55: Appendix A: Block Mode Operation (Oos)
Appendix A Block Mode Operation (OOS) Screens such as shown below (which can be from a 475 Field Communicator, NI Configurator, AMS, DTMs, etc.) can be an indication that the block should be set to Out of Service (OOS): BE57-646 ECLIPSE Guided Wave Radar Transmitter — F fieldbus OUNDATION…
-
Page 56: Appendix B: Transducer Block Tables
Appendix B transducer Block table Item Parameter name Parameter Label BLOCK_STRUCTURE BLOCK STRUCT ST_REV Static Revision TAG_DESC Tag Description STRATEGY Strategy ALERT_KEY Alert Key MODE_BLK Block Mode BLOCK_ERR Block Error UPDATE_EVT Update Event BLOCK_ALM Block Alarm TRANSDUCER_DIRECTORY Transducer Directory TRANSDUCER_TYPE Transducer Type XD_ERROR Transducer Error…
-
Page 57
EOP_THRESHOLD_MODE EoP Threshold Mode EOP_THRESHOLD_VALUE EoP Threshold Value INTERFACE_LEVEL Interface Level INTERFACE_LEVEL_UNIT Interface Level Unit UPPER_THICKNESS Upper Thickness UPPER_THICKNESS_UNIT Upper Thickness Unit UPPER_LIQUID_DIELECTRIC Upper Dielectric IFC_LEVEL_THRESH_MODE Ifc Level Thresh Mode IFC_LEVEL_THRESH_VALUE Ifc Level Thresh Value REJECT_CURVE_STATE Reject Curve State REJECT_CURVE_MODE Reject Curve Mode SAVED_MEDIUM_LOCATION Saved Media Location… -
Page 58
7XK Scale Offset FACTORY_PARAMETER_1 Factory Parameter 1 FACTORY_PARAMETER_2 Factory Parameter 2 FACTORY_PARAMETER_3 Factory Parameter 3 FACTORY_PARAMETER_4 Factory Parameter 4 MAGNETROL_SERIAL_NUMBER Magnetrol S/N DATE_CODE Date Code CONFIG_CHANGED_MODE TB Config Chgd Mode RESET_CONFIG_CHANGED Reset Config Changed USER_PASSWORD New User Password LOCAL_DISP_MEAS_VALUES Local Disp Meas Values… -
Page 59
STATUS_INDICATORS_2 Status Indicators STATUS_INDICATORS_3 Status Indicators STATUS_INDICATORS_4 Status Indicators STATUS_INDICATORS_5 Status Indicators STATUS_INDICATORS_6 Status Indicators TREND_LEVEL_VALUE Level TREND_DISTANCE_VALUE Distance TREND_IFC_LEVEL_VALUE Interface Level TREND_UPPER_THICK_VALUE Upper Thickness TREND_ECHO_STR_VALUE Echo Strength TREND_IFC_ECHO_STR_VALUE Ifc Echo Strength DEVICE_CLOCK Device Clock DEVICE_RUN_TIME Run Time HISTORY_CONTROL History Control HISTORY_CAPTURE_TIME History Capture Time HIST_ENTRY1… -
Page 60
ECHO_HISTORY_LOG8 Echo History 8 ECHO_HISTORY_LOG9 Echo History 9 DELETE_ECHO_HISTORY Delete Echo History SAVE_ECHO_CURVE Save Echo Curve VIEW_ECHO_CURVE View Echo Curve WAVEFORM_SUMMARY Waveform Summary ECHO_CURVE_DATA Echo Curve Data ECHO_DATA_INDEX Echo Data Index DATA_LOG_SETUP Data Log Setup DATA_LOG_SUMM_READ_REQ Log Summary Read Req DATA_LOG_SUMMARY Data Log Summary DATA_LOG_INDEX… -
Page 61
VESSEL_CONICAL_HEIGHT Vessel Conical Height VESSEL_WIDTH Vessel Width VESSEL_LENGTH Vessel Length VOLUME_TABLE_TYPE Volume Table Type LEVEL_INPUT_SOURCE Level Input Source VOLUME_TABLE_LENGTH Volume Table Length VOLUME_TABLE_PT_01 Volume Table Pt 01 VOLUME_TABLE_PT_02 Volume Table Pt 02 VOLUME_TABLE_PT_03 Volume Table Pt 03 VOLUME_TABLE_PT_04 Volume Table Pt 04 VOLUME_TABLE_PT_05 Volume Table Pt 05 VOLUME_TABLE_PT_06… -
Page 62
LEVEL_HIGH_LIMIT Level High Limit ENTER_PASSWORD Enter Password PRESENT_STATUS Present Status STATUS_INDICATORS_1 Status Indicators STATUS_INDICATORS _2 Status Indicators STATUS_INDICATORS _3 Status Indicators STATUS_INDICATORS _4 Status Indicators STATUS_INDICATORS _5 Status Indicators STATUS_INDICATORS _6 Status Indicators TREND_VOLUME_VALUE Volume Flow transducer Block table Item Parameter Name Parameter Label BLOCK_STRUCTURE… -
Page 63
R_TOTALIZER_MODE R Totalizer Mode R_TOTALIZER_MULTIPLIER R Totalizer Multiplier R_TOTALIZER R Totalizer R_TOTALIZER_UNIT R Totalizer Unit R_TOTALIZER_TIME R Totalizer Time RESET_R_TOTALIZER Reset R Totalizer REFERENCE_DISTANCE Reference Distance MAXIMUM_HEAD Maximum Head MAXIMUM_FLOW Maximum Flow LOW_FLOW_CUTOFF Low Flow Cutoff FLOW_ELEMENT Flow Element PALMER_BOWL_FLUME_WIDTH Palmer Bowl Flume Width PARSHALL_FLUME_WIDTH Parshall Flume Width… -
Page 64
FLOW_TABLE_PT_18 Flow Table Pt 18 FLOW_TABLE_PT_19 Flow Table Pt 19 FLOW_TABLE_PT_20 Flow Table Pt 20 FLOW_TABLE_PT_21 Flow Table Pt 21 FLOW_TABLE_PT_22 Flow Table Pt 22 FLOW_TABLE_PT_23 Flow Table Pt 23 FLOW_TABLE_PT_24 Flow Table Pt 24 FLOW_TABLE_PT_25 Flow Table Pt 25 FLOW_TABLE_PT_26 Flow Table Pt 26 FLOW_TABLE_PT_27… -
Page 65
otes BE57-646 ECLIPSE Guided Wave Radar Transmitter — F fieldbus OUNDATION… -
Page 66
otes BE57-646 ECLIPSE Guided Wave Radar Transmitter — F fieldbus OUNDATION… -
Page 67
otes BE57-606 ECLIPSE Model 706 Guided Wave Radar Transmitter… -
Page 68
SERVICE POLICY Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to the purchaser, (or owner) other than transportation cost if: a.
(Ocr-Read Summary of Contents of some pages of the Magnetrol Eclipse 706 Document (Main Content), UPD: 12 March 2023)
-
13, 13 FD_EXTENDED_ACTIVE_1: For error conditions that have been selected in the Extended_Map_1 parameter, this parameter reflects those that have been detected as active. FD_EXTENDED_MAP_1: Allows the user finer control in selecting multiple conditions contributing to a single condition that may be mapped for the various alarm cate- gories. SOFT_SIMULATION_DISABLE: If …
-
37, 37 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ MAIN MENU Pressing any key on the Home Screen will present the Main Menu, consisting of three basic menu labels shown in all capital letters. DEVICE SETUP DIAGNOSTICS MEASURED VALUES As shown, the reverse video represents a cursor identifying the selected item, which will appear in reverse video on the LCD. The actions of the keys at this point …
-
29, 29 BLOCK_ERR_DESC: Reports more specific details regard- ing some errors reported through BLOCK_ERR. 3.3 Input Selector Block (IS) The Input Selector (IS) function block can be used to select the first good, maximum, minimum, or average of as many as four input values and place it at the output. The block supports signal status propagation. (There is no process alarm detection in the Input Selector function block.) ST_R…
-
46, Magnetrol Eclipse 706 46 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ In essence, this approach ensures that the right diagnostic information is available to the right person-at the right time. In addition, it allows diagnostics to be applied, as most appropriate, for a particular plant application (such as process control engineering or asset management mainte- nance). Customer specific mapping of diagnostics to these categories allow…
-
31, 31 TAG_DESC: The user description of the intended applica- tion of the block. STRATEGY: The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block. ALERT_KEY: The identification number of the plant unit. This information may be used in the host for sorting alarms, etc. MODE_BLK: The actual, target, permitted, and normal modes of the block. • Target: The mode to “go to” • Actual: The mode the “block is currently in” •…
-
9, 9 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ 2.2 Resource Block The RESOURCE BLOCK describes the characteristics of the F OUNDATION fieldbus ™ device such as the device name, manufacturer, and serial number. As it only contains data specific to the Eclipse Model 706 FF transmitter, it has no control function. MODE_BLK: Must be in AUTO in order for the …
-
11, 11 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ BLOCK_ALM (Block Alarm): Is used for configuration, hardware, connection, or system problems in the block. The cause of any specific alert is entered in the subcode field. ALARM_SUM (Alarm Summary): Contains the current alert status, the unacknowledged states, the unreported states, and the disabled states of the alarms associated with the block. ACK_OPTION …
-
35, 35 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ 4.2.5 Entering Character Data This method is used for parameters requiring alphanumeric character entry, such as for entering tags, etc. General Menu Notes: 4.3 Password Protection The ECLIPSE Model 706 transmitter has three levels of password protection to restrict access to certain portions of the menu structure that affect the operation …
-
44, 44 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ 5.0 Troubleshooting and Diagnostics The ECLIPSE Model 706 transmitter is designed and engi- neered for trouble-free operation over a wide range of oper- ating conditions. The transmitter continuously runs a series of internal self-tests and displays helpful messages on the large graphic liquid crystal display (LCD) when attention is required. The c…
-
47, Magnetrol Eclipse 706 47 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ Refer to the table below for a complete listing of the Model 706 diagnostic indicators, along with their explanations, default categories, and recommended remedies. N OTES: 1) The remedies shown in this table can also be seen on the transmitter LCD by viewing the present status screen when the device is in a diagnostic condition. 2) Those indicators showing failure as the default result in an alarm condition. �…
-
50, Magnetrol Eclipse 706 50 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ Selecting DIAGNOSTICS from the MAIN MENU presents a list of five ITEMS from the top level of the DIAGNOSTICS tree. When Present Status is highlighted, the highest MAGNETROL priority active diagnostic indicator (numer- ically lowest in Table 5.1.3) is displayed on the bottom LCD line as shown above. Pressing the ENTER key moves the activ…
-
28, Magnetrol Eclipse 706 28 GRANT_DENY: Options for controlling access of host computers and local control panels to operating, tuning, and alarm parameters of the block. INPUT_OPTIONS: Option bit string for handling the status of the auxiliary inputs. IN: The block input value and status. IN_LO: Input of the low range transmitter, in a range extension application. IN–1, IN–2, IN–3: Inputs combined with the PV in a section of four term math functio…
-
30, 30 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ IN_2: The block input value and status. IN_3: The block input value and status. IN_4: The block input value and status. DISABLE_1: Parameter to switch off the input from being used 0- Use, 1 — Disable. DISABLE_2: Parameter to switch off the input from being used 0- Use, 1 — Disable. DISABLE_3: Parameter to switch off the input from being used 0- Use, 1 — Disable. DISABLE_4: Parameter to switch off the inp…
-
68, IMPORTANT SERVICE POLICY Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to the purchaser, (or owner) other than transportation cost if: a . Returned within the warranty period; and, b. The fact…
-
20, 20 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ Below are shown some examples of various typical AI Block configurations. Probe PL [in / cm] Probe Length = PL Inches orcm Transducer Block + LCD Level AI Block Output [To FF segment] 100% 0[in / cm] 0% Probe Probe Length 111 cm 81.3 cm 0cm 100% 0% Offset = –15.5 cm Transducer Block + LCD Level AI Block Outp…
-
21, 21 BE57-646 ECLIPSE Guided Wave Radar Transmitter — FOUNDATION fieldbus ™ The ECLIPSE Model 706 with FOUNDATION fieldbus ™ supports the Simulate feature in the Analog Input block. The Simulate feature is typically used to exercise the opera- tion of an AI block by simulating a TRANSDUCER block input. This feature cannot be …
-
5, 5 1.2 Device Description (DD) An important requirement of Fieldbus devices is the concept of interoperability, defined as “the ability to operate multiple devices in the same system, regardless of manufac- turer, without loss of functionality.” Device Description (DD) technology is used to achieve this interoperability. The DD provides extended descriptions for each object and provides pertinent information needed by the host system. DDs a…
|
|
Related Devices:
|
Types of Manuals:
The main types of Magnetrol Eclipse 706 instructions:
- User guide — rules of useing and characteristics
- Service manual — repair, diagnostics, maintenance
- Operation manual — description of the main functions of equipment
Transmitter Instructions by Magnetrol:
-
Endress+Hauser Proline 300
Products Solutions ServicesBrief Operating InstructionsProline 300EtherNet/IPTransmitter with Coriolis sensorThese instructions are Brief Operating Instructions; they arenot a substitute for the Operating Instructions pertaining tothe device.Transmitter Brief Operating InstructionsContain information about the transmit …
Proline 300 Transmitter, 40
-
Sennheiser 04484
Headphones & Accessories 1Open, circumaural headphones (packaging languages:German/Italian)HD 500Publ.: 23.09.2002Cat. No. 04484DescriptionThe HD 500 Fusion is a pair of open dynamic hi-fi stereoheadphones with clear, accurate tonal quality. They feature asingle-sided, highly conductive OFC copper cable, Duofoldiap …
04484 Headphone, 1
-
Zaxcom TRX900
Zaxcom Digital Wireless System TRX900 TRX900AA TRX80 RX4900 8.76 5.98 & 5.98T Fax: 973-835-6633 Email: [email protected]’s Manual 0 TRX700 TRX992 RX900 (M/S) …
TRX900 Microphone, 99
-
HACH LANGE si628 C
DOC023.98.90242Transmitters si628 C© HACH LANGE GmbH, 2010, All rights reserved. Printed in SpainManualBedienungsanleitungManualManuel d’utilisateurManuale di istruzioni05/2010, Edition 1 05/2010, Heft 1 05/2010, Edición 105/2010, Edition 105/2010, Edizione 1si628 C_HACH LANGE_Ed. 0510.indd IND:1si628 C_HACH LAN …
si628 C Transmitter, 127
-
Flight Display Systems FD900X3B
Document Number: MAN – FD900X3B Ver B Rev: A Revision Date: 02/02/2011 Page 1 of 11 FD900X3B Ver B Installation and Operation Manual 28VDC Wireless Audio Transmitter TECHNICAL SUPPORT 678-867-6717, or www.FlightDisplay.com …
FD900X3B Transmitter, 11
-
Shure MX692
Model MX692User GuidePrinted in U.S.A.27A8828 (CE)©2003 Shure IncorporatedSHURE MX692 WIRELESS BOUNDARY MICROPHONE TRANSMITTER• Integrated functionality of Microflexcardioid cartridge with UC1 UHFwireless transmitter• Frequency agile transmitter offers191 user selectable channels forboth UA and UB country codes• …
MX692 Transmitter, 18
-
Danfoss MBT 9110
Document type Myriad Pro Semibold 7 pt.Product name — Myriad Pro bold 12/12 Product type — Myriad Pro light 12/12 xxxRxxxxbar code place holderxxxRxxxxbar code place holder© Danfoss | DCS (xxx) | YYYY.MM — Myriad Pro Regular 7 pt.XXXX.XX.XXX.XX.XX.XXX | XXXAXXXX | 1 Temperature transmitter MBT 9110 — 084Z7443 Oper …
MBT 9110 Transmitter, 32
Documents: (3) Magnetrol Eclipse 706 Transmitter PDF User Manuals and Service Instructions
| # | Screen | Document Information | Share in Social |
|---|---|---|---|
| 1 |
|
Magnetrol Eclipse 706 Installation and operating manual (108 pages) Magnetrol Eclipse 706 Magnetrol Eclipse 706GWR Installation And Operating Manual Transmitter 108 |
|
| 2 |
|
Magnetrol Eclipse 706 Operating manual (68 pages) Magnetrol Eclipse 706 68 |
|
| 3 |
|
Magnetrol Eclipse 706 Operating manual (124 pages) Magnetrol Eclipse 706 124 |
Transmitter Appliance:
More Products:
- Enhanced Model 705
- Jupiter JM4
- STI R95
- E3A Modulevel
- Orion Jupiter Enchanced 2 Series
- Eclipse 706-512
- Pulsar R96
- Kotron Sentinel II 804 Series
- eclipse 705
Related Instructions for Eclipse 706:
Categories of Magnetrol Devices:
Transmitter
Measuring Instruments
Radar
Control Unit
Switch
Kitchen Appliances
Controller
Industrial Equipment
Eclipse
™
1.1 Overview………………………………………………………….4
2.1 Overview………………………………………………………….7
2.3.4 Model 706 FF Device-Specific
2.5 PID Block ………………………………………………………21
BE57-646 ECLIPSE Guided Wave Radar Transmitter — F
®
Model 706 GWR transmitter
with F
OUNDATION
…………………………………………..4
™
OUNDATION
Fieldbus
™
5.1 Diagnostics……………………………………………………..44
fieldbus
™
Output
3